Issue:
Difference between a EGX100SD and a EGX100MG.

Product Line:
EGX100SD and EGX100MG Ethernet Gateways

Environment:
All

Cause:
Need Ethernet communication with a Drive's or Soft Starter's Modbus port

Resolution:
The EGX100SD has a Square-D label. The EGX100MG has a Merlin Gerin label.

Issue:
OBF fault on a ATV320

Product Line:
Altivar 320

Environment:
All

Cause:
OBF fault on drive display

Resolution:
Possible causes:
• Braking too sudden or driving load.
• Supply voltage too high.

Remedies:
• Increase the deceleration time.
• Install a braking resistor if necessary.
• Activate the [Dec ramp adapt.] (brA) function page 172, if it is compatible with the application.
• Check the supply voltage.

Product Line
3090SCCT

Environment
CT Ratio

Resolution
*Warning: Installation and maintenance of this device should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Failure to follow the instructions / warnings in the Meter Installation Guide can result in permanent damage to the meter, severe injury or death.

Note: This is not a suggested solution. It is recommended that the appropriate CTs be purchased for each application.

The ratio assigned to a current transformer is based on the assumption that the primary conductor will only pass through the current transformer opening once. It is possible to reduce the rating by looping the primary conductor through the opening multiple times. The rating will be reduced by the times the primary conductors is looped through the CT. For example, a CT with the rating of 400:5A will be changed to 100:5A if four loops or turns are created by passing the primary conductor through the CT four times. See illustration and table below.

The ratio of the current transformer can also be modified by changing the number of secondary turns by either passing the secondary lead forward or backward through the current transformer opening.

Ip / Is = Ns / Np

Ip = primary amperage
Is = secondary amperage
Ns = number of secondary turns
Np = number of primary turns

400p / 5s = 80s / 1p

Note: One turn is dropped from the secondary as a ratio correction factor.

By adding secondary turns, while keeping the primary amperage the same will result in greater secondary output. For example, using the 400:5A current transformer, by adding 5 secondary turns it will now require 425 amps on the primary to maintain the 5 amp secondary output.

400p / 5s = 80s / 1p
Xp / 5s = 85s / 1p , where Xp equals the primary amperage.
Solving for Xp gives a requirement of 425 amps on the primary.

Similarly, subtracting 5 secondary turns will now require 375 amps on the primary to maintain the 5 amp secondary output.

400p / 5s = 80s / 1p
Xp / 5s = 75s / 1p , where Xp equals the primary amperage.
Solving for Xp gives a requirement of 375 amps on the primary.

Issue
A user would like to know the default IP address, subnet mask, gateway, and credential information for an EGX100 or EGX300

Product Line
EGX100, EGX300

Environment
Communications

Cause
Default communication parameters are needed to establish connection to the EGX100

Resolution
The default communication parameters are:

Default IP address 169.254.0.10
Default Subnet Mask 255.255.0.0
Default Gateway 0.0.0.0
Default Username Administrator
Default Password Gateway
Default Frame Format Ethernet II
Default Media Type 10T/100Tx Auto
Default Obtain IP Address Automatically Disabled

Issue
BLAT is configured on server to send out email using the Launching Module in VIP. The SMTP server has changed and need to reconfigure in BLAT.

Product Line
SPM7.x
PME7.x
Power Monitoring Expert (PME 8.x)

Environment
Windows

Cause
BLAT is configured on server to send out emails using the Launching Module in VIP. The SMTP server has changed and need to reconfigure BLAT

Resolution
When BLAT was configured on the server the install command only stores the various parameters in the Windows Registry. To change or verify the SMTP settings navigate to Regedit ->HKEY_LOCAL_MACHINE ->SOFTWARE ->Wow6432Node ->Public Domain ->Blat. The configured parameters that BLAT uses can be found here.

Issue:
Is the shorting contactor for an ATS48 a required component?

Product Line:
Altistart 48

Environment:
All

Cause:
NA

Resolution:

A shorting contactor engages when the motor is running at full speed.  The starter provides proper sequencing of this contactor by the ``end of starting`` relay (R2).  When the start is completed, the shorting contactor will be commanded to close.  The starter will continue to monitor the motor thermal state and provide motor overload protection.  Upon a stop command, the KM3 (shorting contactor designation) contactor will open, transferring the motor current to the SCRs to allow for a controlled deceleration if desired.

The shorting contactor is not required, but there are definite advantages to using one:

  • It extends the life of the internal electronics and SCRs due to the reduced heat effects of the current and SCR firing.
  • It reduces the heat dissipated by the controller.

Issue:
Trying to save the parameters in the keypad and upload them to another identical ATV630 drive.

Product Line:
ATV630 drives

Environment:
Keypad

Cause:
Transferring files

Resolution:
Go to Main menu and scroll down to menu 7: File Management and press Ok.
Select 7.1-Transfer config file- select copy from the drive ( to save to the keypad) or select Copy to the drive (to upload the keypad setting to the drive).

Issue:
Can I simulate PTO function blocks in SoMachine Basic?

Product Line:
M221, TM221

Resolution:
Just like the PID blocks, you cannot simulate PTO functions blocks in SoMachine Basic. You will need an actual M221 hardware controller to test the PTO functionality

Our 115/230V dual voltage Ultimate shaver sockets are rated IP41 and are manufactured to BS EN 61558-2-5.

Issue:
How does humidity affect insulation resistance testing results?

Product Line:
Circuit Breakers

Environment:
Molded case and insulated case breakers

Resolution:
High humidity can drastically reduce insulation resistance testing results for circuit breakers.

Some equipment acceptance testing documents suggest values above 100 mega ohms and normally that is okay however high humidity can drastically reduce the results of the insulation resistance values.  Below is a sample of how higher humidity can reduce the IR values, making the 100 mega ohms acceptance testing values invalid.
40% humidity:  breaker IR value above 500 mega ohms, typical 1 G ohm*
75% humidity:  breaker IR value around 10 mega ohms*
95% humidity:  breaker IR value around 4 mega ohms*

*All values above are functional and conforming. Values derived from test data on Powerpact H frame breakers in a Schneider Electric laboratory.

The IEC 60947 standard, section 6.1.3.1 states that IR testing should be done below 50% humidity and states a 1 M ohm minimum IR value for a new breaker.

NEMA AB-4 recommends IR values for breakers, less than one mega ohm (1,000,000 ohm) should be investigated.  The Schneider Electric field testing and maintenance guide also states the same one mega ohm value, as written below.

Severe environmental conditions can reduce the dielectric strength of
molded case circuit breakers. Check insulation resistance during electrical
system testing.
To check the insulation resistance, perform the following steps:
1. De-energize and isolate the circuit breaker.
2. Clean the circuit breaker as described earlier.
3. Using a megohmmeter with a capacity of 500–1000 Vdc, apply voltage
from:
a. Each phase-to-ground with the circuit breaker on (circuit breaker
contacts closed).
b. Phase-to-phase with the circuit breaker on (circuit breaker contacts
closed).
c. Between each line and load terminal with the circuit breaker off
(circuit breaker contacts open).
4. Record resistance values. Resistance values of less than one mega ohm
(1,000,000 ohm) should be investigated.

Issue:
VMware ESXi host, which is running the free edition of VMware, is not shutting down when commanded to by PowerChute Network Shutdown.

Product Line:
PowerChute Network Shutdown (PCNS) version 2.2.3, 2.2.4, 3.0, 3.0.1, 3.1, 4.x

Environment:
VMware ESXi versions 3.5, 4.x, 5.x, 6.x, 7.x

Cause:
The free edition of VMware ESXi provides read-only access to the API functions. Without write access to the API functions, PowerChute cannot issue a command to shut down an ESXi host.
To review a list of supported VMware ESXi versions see What VMware ESXi Licenses are support with PowerChute?

Resolution:
To make PowerChute Network Shutdown work properly you will need to purchase a license for ESXi.

You can also find more information in Kbase Shutdown VMware ESXi 4.X, 5.X unlicensed server with PowerChute Network Shutdown.

Issue
What is the part number for PM800 hardware kit?

Product Line 
PM800 Series (PM810, PM820, PM850, PM870)

Cause 
Customer wants to order connectors for PM800 series meter (like voltage input connector, Power Supply Connector, and ect.)

Environment 
Mounting connectors on PM800 series meter

Resolution
The part number for PM800 hardware kit is 63230-500-16.

The Kit contains the following hardware:

1- Meter template for the cutout = part # 63230-500-09
1- KYCS Output/Input connector = part # 63230-500-29
1- RS485 2 wire connector = part # 63230-500-30
1- Control Power Connector = part # 63230-500-31
2- Retainer spring clips for mounting = part # 63230-500-38 (NOTE: This part number is compatible only with integrated display meter only)
1 - 2-Wire RS485 Terminator MCT2W =63230-500-59
1- Voltage input connector = 63230-500-28

Please review document attach along this article which shows pictures of each connectors and where do they mount on PM800 series meter.

Issue
Part number for PM800 series remote display kit

Product Line
PM800 series

Environment
Part Numbers

Resolution
The part number for the PM800 series meter remote display kit is PM8RD. This part number includes the remote display, the cable (CAB12) and the 4-wire, RS232/485 communication module.
Please note there is no commercial part number for just the remote display itself. The part number for the PM800 series meter remote display adapter is PM8RDA.

The PM800 series has passed the end of commercialization period and therefore distributors may or may not carry the parts.

Issue
What is the part number for a CT shorting terminal block?

Product Line
Power Meter Accessories

Environment
All meter applications with current over 5 Amps which require Current Transformers.

Cause
Information needed on shorting terminal blocks

Resolution

For a 4-pole shorting block it is 3090TB4 and for the 6-pole it is 3090TB6

UPDATE Year 2014
Going forward any 3090TB4 or 3090TB6 Shorting Terminal Block ordered will be Cooper Bussmann branded and not Marathon branded.
3090TB6 = Cooper Bussman model KUXSC6S2644
3090TB4 = Cooper Bussman model KUXSC4S2644
*Cutsheet attached below*

The shorting screws for the 3090TB4 and 3090TB6 CT shorting blocks can be purchased from "Marathon Special PRODUCTS"
The part number for the shorting screws is "9616901". Both the 4-pole and 6-pole CT shorting blocks require a quantity of 4 of the provided screws part number.


Internal PMO/PMC
All content © 1992-2007 Schneider Electric

text
text text
text text

Legacy KB System (APS) Data: RESL185215 V2.0

Issue:
ASi bus connector for the TSXSAY100, TSXSAY1000 and 140EIA92100 modules

Product Line:
TSXSAY100, TSXSAY1000, 140EIA92100

Resolution:
We do not have a part number for this connector and cover assemble that the customer can order from SE.
We do have the vendors part number for just he connector, it is Phoenix Contact number 1841909.
We also can internally order them from France, the part number is W815891970101A.

Goals and Symptoms 
Currently, HMI Products like Magelis GTO and Magelis GTU can be conformal coated as a Service by Schneider-Electric, but the specifications are not communicated to the customers.
The goal of this resolution is to provide the coating compatible specifications for HMIGTO and HMIGTU.
Causes and Fixes       
Attached, please find the documentation about the coating compatible specifications for HMIGTO and HMIGTU.

Issue:

Looking for a driver in VIjeo Designer or EcoStruxure Operator Terminal Expert that can communicate to LOGO! Smart Relay from Siemens

 

Product Line:

Harmony, Magelis, Vijeo Designer, EcoStruxure Operator Terminal Expert

 

Resolution:

Today, none of the Harmony or Magelis HMI's are able to communicate to a Siemens LOGO! Smart Relay. We currently only support communication to Siemens LOGO! PLCs. The recommendation is to verify with Siemens if the smart relay is able to communicate with Modbus TCP/IP or Modbus RTU. If so, then our HMIs could use the Modbus protocol to communicate to this relay.

Issue:
Which Magelis HMIs can use the battery part number: HMIZGBAT?

Product Line:
backup battery, HMIGTO, HMIGTU

Resolution:
HMIZGBAT battery is for the Magelis HMIGTU and HMIGTO series except HMIGTO1300 / 1310 / 2300 targets.

Issue:
The Vijeo Designer Web Gate server does not support secure HTTP connections.

Product Line:
XBTGT, XBTGK, HMISTU, HMISTO, HMIGTO, HMIGK, HMIGTU, iPC

Resolution:
The Magelis HMIs do not support HTTPS (secure connections). Connect via Web Gate to the Magelis HMIs with HTTP only.

To substitute old XBTGTxx40 MultiMedia , we have done successful tests with Analog camera on Magelis HMIG5U2.
Using a Analog/ USB converter  from Imaging Source Company ( ref =DFG/USB2pro ) you can connect Analog Camera PAL/NTSC to Magelis GTU with Open box HMIG5U2 ;
This converter is distributed worldwide.

  • You  can re-use the VijeoDesigner XBTGTxx40 application and to convert it on HMIG5U2 Box with selection of the same display size than XBTGT !
  • You have same Video functions : Live Video Display , Record & Replay functions
  • You have also to install manually  on the HMIG5U2 the Windows drivers from imaging Source to control the converter.

Issue:
Is it possible to increase the lifespan of the Magelis HMI screen by turning down the brightness?

Product Line:
XBTGC/GK/GT, HMIGTO/GTU/STO/STU, Box PC, Panel PC, Magelis, HMI, life cycle

Environment:

Cause:

Resolution:
When current applied the backlight is decreased, lifetime will be extended.  However, power is always provided to the LCD panel, even if LCD entering Standby and Sleep mode.  Therefore, there is no way to extend the lifetime of the screen.

Issue:
Is there a Prescription toolkit document (Recommended Technical Specification) for the Magelis HMIs?

Resolution:
As of 2/5/2016, attached is the latest Prescription document for the Magelis HMIs.

Issue
Are the Flicker values valid for a Delta, 2PT and 2CT system?
In a Delta configuration can you base flicker measurements off of 3 PTs instead of 2?
Can the Flicker module be made read-only?
How to get flicker data?

Product Line
ION7550
ION7650
ION8600
ION8650
ION7400Environment
ION flicker measurements

Resolution
Are the Flicker values valid for a Delta, 2PT and 2CT system?

We are not aware of any standards that stipulate that the flicker values need to be based on voltage phase line to neutral values. As such, when the meter is in delta mode, the Flicker module in the meter detects this volts mode and calculates flicker data based on voltage line-to-line values. The accuracy of the calculation is the same whether line-to-neutral or line-to-line voltages are used.

In a Delta configuration can you base flicker measurements off of 3 PTs instead of 2?
No. In delta mode only 2 PTs are required for V1 and V3 connections; V2 is calculated based off these values. The Flicker module also uses the calculated V2 voltage to generate flicker data.

Can the Flicker module be made read-only?
The hardware-locked ION meter option locks all revenue related modules in the meter however the Flicker Module is not included in the locked modules. One way to restrict access to the Flicker module on the meter would be to enable Advanced Security and grant a user read-only access.

How to get flicker data?
The outputs of the Flicker Module need to be connected to a Data Recorder module in order to record flicker data.
General information regarding the Flicker module and the Data Recorder module is available in the online ION Reference document.

The scale factor for the Energy reading in the Series 700 Power Meter is automatically adjusted by the meter. The front display will adjust based on the range of the reading. There is a scale register associated to Energy but is not user adjustable. Energy is stored in a 2 register format as a floating point value. Other Meters like the Series 2000, 3000, 4000 Circuit Monitors and the Series 800 Power Meter store Energy in 4 registers with a Modulo 10,000 (mod10) format.


  • Original article# 4712
    Date Created: Unknown
    Last Revised: March 19, 2008
    Public
    Original Author: PMOZONE
    All content © 1992-2008 Schneider Electric

Legacy KB System (APS) Data: RESL184650 V2.0, Originally authored by DaMi on 06/17/2007, Last Edited by PhHa on 03/20/2008
Related ranges: PM700 series

Issue
Does the Power Meter Series 600 Display require it's own firmware?

Product Line
PM600

Environment
Firmware

Resolution
The Power Meter display works as a terminal remotely connected to the Power Meter. The firmware that tells the display what to do is stored in the Power Meter base. No additional firmware is required.

See FA313600 for the meters firmware.

Issue
Does the pinout for the display cables match between the Power Monitor and circuit monitor

Product Line
CM3000
CM4000
PM800
PM600

Environment
Cabling Pinout

Resolution
This depends on the model number of the meters in question. The CM3000, CM4000, and PM800 all use the same display cable. The PM600, on the other hand, uses a different pinout and will not function properly with a CM3/CM4/PM8 display cable. Despite the different pinouts, both display cables utilize a 6 pin RJ-11 jack with 26 AWG wire. Both cables are RS-232, thus 50ft is the maximum length. If the displays or cables are interchanged, no damage will occur. The pinouts are shown below:

Issue
Do meters require periodic re-calibration and if so, how often?

Produce Line
Power Metering

Environment
Meter calibration and accuracy

Resolution
All meters are calibrated at the factory to ensure they comply with published accuracy specifications. They do not require periodic re-calibration nor should they need to be re-calibrated over the operational life of the meter. However, some meters may experience an accuracy drift over time due to environmental or other unknown factors. If a meter is suspected to have drifted outside of it's published accuracy range, it can be sent back to the factory for re-calibration and certification.

 

Issue
How to upgrade the firmware on a PM800, PM5XXX, PM200, PM700, PM600, CM4000/T, CM3000 and CM2000 series (Powerlogic) meter.

Product Line
PM600 series power meter
PM700 series power meter
PM800 series power meter
PM5000 series power meter
CM4000 series power meter
CM3000 series power meter
CM2000 series power meter

Environment
Firmware Upgrade

Resolution
*Warning: The firmware utilities listed here can cause permanent damage to your product if applied incorrectly. Before downloading any firmware updates, verify the firmware you are downloading is appropriate for the specific model number of your product. If you have any doubts, contact Technical Support for guidance.* 

*Warning: Devices should be disconnected from all monitoring software before performing a firmware upgrade*

Reference the embedded video and attached documents for detailed instructions when using DLF-3000 to upgrade CM4000, PM800, and PM5000 series meter firmware.

The attached procedure is specific to upgrading firmware on the PM800 and PM5000 meters, however the concept and guidelines will be similar for the following meter types in the Powerlogic family:
CM4000 Series
CM3000 Series
CM2000 Series
PM800 Series
PM600 Series
PM5000 Series

  • To upgrade a CM4000/4250, load the firmware files in the following order using DLF-3000:

1- CM4_DL_XXXXX.fw
2- CM4_OS_XXXXX.fw
3- CM4_LL_XXXXX.fw

If it is a CM4000T, install CVMT_OS_XXXXX.fw after upgrading the CM4_LL_XXXX.fw file.

  • To upgrade CM3000 series, load the firmware files in the following order using DLF-3000:

1- CM3_DL_XXXXX.fw
2- CM3_OS_XXXXX.fw
3- CM3_LL_XXXXX.fw

Use the following link to download the DLF-3000 software:
DLF3000 Download

It is important to note that you need to right click and run DLF3000 as an administrator.

The following links is to the latest firmware for a CM4000 Series meter (v16.010) and CM4 CVMT OS_11.210:
CM4 DL 13.000
CM4 OS 16.010
CM4 LL 14.170
CM4 CVMT OS 11.210

The following links is to the latest firmware for a CM3000 Series meter (v15.030):
CM3 DL 12.200
CM3 OS 15.030
CM3 LL 14.170

The following link is to the latest firmware for a CM2000 Series meter (v17.011):
PowerLogic CM2000 (CM2) Firmware version 17.011 for use with DLF3000 and DLF101 (fix for rapid energy accumulation on previous versions of firmware)

The following link is to the latest firmware for a PM210 Series meter (v3.150):
PM210 firmware

The following link is to the latest firmware for a PM710 Series meter:
PM710 firmware (V3.150)
PM750 firmware (V3.160)

The following link is to the latest firmware for a PM800 Series meter (v12.700):
PM800 firmware

The following link is to the latest firmware for a PM600 Series meter:
PM600 series firmware 
**NOTE: PM600 series firmware has two options in the above link. Please confirm the correct one is used on your device with the instructions in the link.

The following link is to the latest firmware for a PM5100 Series meter (v2.1.1 and v2.2.1):
PM5100 firmware

Firmware version 2.xx is not compatible with firmware version 1.xx. The following link is to the latest V1.xx firmware for a PM5100 Series meter (v1.5.4 and v1.6.4):
PM5100 V1 firmware

The following link is to the latest firmware for a PM5300 Series meter (v2.1.1 and v2.2.1):
PM5300 firmware

Firmware version 2.xx is not compatible with firmware version 1.xx.The following link is to the latest V1.xx firmware for a PM5300 Series meter (v1.5.4 and v1.6.4):
PM5300 V1 firmware

The following link is to the latest firmware for a PM5560 Series meter that used DLF-3000 for the upgrade (v1.01.0):
PM5560 firmware

All future upgrades past v1.01.0 use the FTP server for the upgrade. See the PM5500 User Guide Page 139 or follow FA299853.

​More Information: 
OS-Operating system;
RS-Reset system;
DL-Download system;
LL-Language Library

Title
M580 CPU EIP Adapter capability
Issue
Need procedure to configure the EIP Adapter capability of a M580 CPU.
Product Line
Modicon Quantum
Environment
ODVA Ethernet/IP
Cause
User configurable capability.
Resolution
The M580 CPU supports up to 3 instances of local Adapters (Local Adapter 1, Local Adapter 2, and Local Adapter 3).

To Access settings:

  1. Double-click the M580 CPU communication DTM in the Unity Pro DTM Browser.
  2. In the navigation tree on the left side of the Device Editor window expand the EtherNet/IP Local Adapters.
  3. Select one of the three available local Adapters.
To Configure parameters:
  1. Activate and name the local Adapter.
  2. Specify the size of the local Adapter input and output assemblies.

Title
Modicon M580 IO Scan nodes on different domains

Issue
Modicon M580 IO Scan nodes on different domains

Product Line
M580

Environment
Unity Pro 11.1

Cause
N/A

Resolution
It is not possible to IO Scan devices that are located on different domains with the M580 built-in Ethernet port or the BMENOC0301.2 module. Unity pro will display an error saying both IP and gateway should have the same subnetwork mask. To IO Scan devices in different domains requires the use of a BMENOC0301.3  with Unity pro V11.1.

Issue
The difference between the M580 PAC BMEXBP backplane's two types of connectors, Ethernet and X Bus

Product Line
Modicon M580 PAC BMEXBP

Environment:
EcoStruxure Control Expert
Unity Pro

Resolution
The Modicon M580 PAC BMEXBP backplanes have two types of connectors, Ethernet and X Bus.
The X Bus connection present on all M580 racks is the vary same that is used on the M340 backplane.
It is used for to obtain and exchange the below type of data with the M580 CPU:
1.  Configuration data for the X80 modules
2.  Application and diagnostic data

The BMEXBP backplane Ethernet connector is used for:
1. eX80 I/O modules, which require an Ethernet bus on the rack in order to exchange data (for example, X80 HART modules)
2. Communications to third-party modules that require Ethernet
3. Ethernet communication modules that interlink to the M580 CPU

Issue:
What is the Maximum number of BMXNOR0200 module which can be installed with a Modicon M580 CPU local rack?

Product Line:
BMXNOR0200H

Environment:
All

Resolution:
The maximum number of BMXNOR0200 which can be installed within a local rack containing M580 CPU is 6.
It also depends on the model of M580 CPU is being used.

1. BMEP58 6040 can accommodate 6 BMXNOR0200 modules.
2. BMEP58 5040 can accommodate 4 BMXNOR0200 modules.
3. BMEP58 4040 can accommodate 4 BMXNOR0200 modules.
4. BMEP58 4020 can accommodate 4 BMXNOR0200 modules.
5. BMEP58 3040 can accommodate 3 BMXNOR0200 modules.
6. BMEP58 3020 can accommodate 3 BMXNOR0200 modules.
7. BMEP58 2040 can accommodate 2 BMXNOR0200 modules.
8. BMEP58 2020 can accommodate 2 BMXNOR0200 modules.
9. BMEP58 1020 can accommodate 2 BMXNOR0200 modules.

Issue:
Can we use BMENOP0300 in the M580 ePAC redundant configuration?

Product Line:
M580
X80 IO

Environment:
EcoStruxure Control Expert
Unity Pro

Resolution:
Yes. BMENOP0300 can work with both stand-alone and redundant ePAC systems and all M580 CPU types.

Issue:
How do I configure a Write_Var block to send Modbus requests to an RTU device on a TCP Gateway the with BMXNOC0401 or BMENOC03X1 communication modules?

Product Line:
M580
M340

Environment:
EcoStruxure Control Expert
Unity Pro

Resolution:
See below an example of Write_Var block for writing Modbus slave data through ETG100 gateway.​

In ADDM block '0.3.0{192.168.1.21}1.TCP.MBS' where
Rack = 0
NOC module slot address = 3
Channel = 0
Gateway IP address = 192.168.1.21
Modbus slave id = 1
Message type = TCP
Protocol = Modbus​(MBS)

In Write_Var block
OBJ: String declaring the type of object to write (%MW or %M)
Num: Index of the first object to write
NB: Number of objects to write
EMIS: Data to write
For more details check attached unity help documents.​

Title

M580 Communications capability
Issue
Explain the communications capability of the M580 PLC.
Product Line
Modicon M580
Environment
Unity 8.0 or greater and Control Expert
Resolution
The M580 PLC supports both Implicit and Explicit communications. Implicit communications is setup through the DTM Browser. The DTM Browser allows the creation of Distributed IO connections and requests through the use of EDS or DTM files for the remote node communication setup. Implicit exchanges are performed automatically on each cycle of the task.
Explicit exchanges are performed on application request. They use specific function blocks. An acknowledgment or reply is sent once the requested action is performed. This reply may be received a few cycles after the request was sent.

Title
M580 USB Communications capability
Issue
Need explanation of the USB communications setup of the M580 PLC.
Product Line
Modicon M580
Environment
Unity, Control Expert
Resolution
The M580 USB RNDIS driver uses a Ethernet type connection, this requires assigning the IP address of  90.0.0.2 to the Ethernet connection created by the installation of the M580 USB drivers in the computer's Network Connections .

Issue
Allen Bradley communications

Product Line
Modicon M580

Environment
Control Expert
Unity Pro

Resolution
The M580 can send an explicit Ethernet IP message to a Contrologix PLC as long as it is sent to an Ethernet/IP object that supports being read or written.
Note: You will need to talk to the Contrologix PLC support on what Ethernet/IP objects a remote Ethernet/IP Scanner device can read or write.

Contrologix PLCs can read and write each others Tag database via Ethernet/IP using the proprietary Client Server Protocol ("CSP") protocol, with embedded PCCC  (Programmable Controller Communication Commands) commands. This Ethernet/IP (CSP/PCCC) protocol is a proprietary implementation of Ethernet/IP and Schneider Electric does not have access to it.

Issue:
What were the results of the M340 Series PLC RADIO FREQUENCY IMMUNITY TEST?

Product Line:
Modicon M340, BMXP34

Resolution:

The results are based on λ/4 or  λ/8 antenna and the worst case calculated (when the field is reflected and the PLC catches the incoming field + the reflected field.)

Antenna  λ/8 @ 1 meter
1. VHF radio transmitter – nominal 47 MHz to 48 MHz – rated 15 W minimum RF output to antenna. worse case field 2*E0 = 7,7
2. VHF radio transmitter – nominal 158 MHz to 173 MHz – rated 10 W minimum RF output to antenna. worse case field 2*E0 = 6,3
3. UHF radio transmitter – nominal 450 MHz to 470 MHz – rated 5 W minimum RF output to antenna. worse case field 2*E0 = 4,5
4. UHF radio transmitter – nominal 832 MHz to 848 MHz – rated 0.6 W minimum RF output to antenna. worse case field 2*E0 = 1,5

Antenna  λ/4 1 meter
1. VHF radio transmitter – nominal 47 MHz to 48 MHz – rated 15 W minimum RF output to antenna. worse case field 2*E0 = 25,6
2. VHF radio transmitter – nominal 158 MHz to 173 MHz – rated 10 W minimum RF output to antenna. worse case field 2*E0 = 20,9
3. UHF radio transmitter – nominal 450 MHz to 470 MHz – rated 5 W minimum RF output to antenna. worse case field 2*E0 = 14,8
4. UHF radio transmitter – nominal 832 MHz to 848 MHz – rated 0.6 W minimum RF output to antenna. worse case field 2*E0 = 5,1

- We do radiated immunity tests according to IEC61000-4-3 in a semi-anechoic chamber and the field is measured in V/m.
- For industrial products, we shall comply to 10V/m in the range 30MHz to 2GHz; 3V/m in the range 2GHz to 6GHz
- During the test, the product shall continue to work without any issue when the field is applied without any condition of duration with the antenna positioned vertically, then horizontally, in front of the products, and two sides and back.
- When we do our tests on the M340 range, we make a sweep @15V/m from 80MHz to 3GHz.

In conclusion, there is a risk if the power of the walkie-talkie is over 5W and distance below 1 meter.

There are four sizes of racks, chosen according to the number of modules you wish to use: The list above gives the number of usable slots.

BMXXBP0400 rack (4 slots)
BMXXBP0600 rack (6 slots)
BMXXBP0800 rack (8 slots)
BMXXBP1200 rack (12 slots)

Ethernet Racks
Ethernet racks have all the features of the X Bus racks with the addition of an Ethernet communication bus across the backplane.
The M340 can use the BMEXBP racks However the Ethernet connection is not used in Modicon M340 architectures.

BMEXBP0400, BMEXBP0400H  - 4 slots
BMEXBP0800, BMEXBP0800H  - 8 slots
BMEXBP1200, BMEXBP1200 H  - 12 slots (1)
BMEXBP0602, BMEXBP0602H  - 6 slots (2)
BMEXBP1002, BMEXBP1002H  - 10 slots (2,3)

(1). This rack has eight slots with X Bus and Ethernet connectors plus four slots (slot numbers 02, 08,10, and 11) with X Bus connector only.
(2). Dual power supply racks are compatible with the BMXCPS4002 redundant power supply.
(3). This rack has eight slots with X Bus and Ethernet connectors plus two slots (slot numbers 08 an 02) with X Bus connector only

Issue

IO scanning 3x input registers

 

Product Line

Modicon M340

 

Environment

EcoStruxure Control Expert

 

Resolution

You can only use IO scanning for 4x holding registers. If you need to read 3x input words you will need to use the READ_VAR and set the OBJ to %IW.

 

Issue
Looking for replacements for the connectors that were included with the BMXCPSxxxx power supply purchase.

Product line
Modicon M340, Modicon X80

Resolution
Below is the replacement  part number of the M340 Power Supply Connectors:

Part numbers with description
MPCYN00CF100N- CF card 128 MB
MPCYN00CF152R- 1GB CF for Smart iPC 15' (MPCST52NDJ0*) loaded with Windows Xpe SP2 in 6 languages and Vijeo D Runtime
MPCYN00CF152T- 1GB CF for Smart iPC 15' (MPCST52NDJ0*) loaded with Windows Xpe SP2 and Web App
MPCYN00CF200N- Blank CF 2 GB for Smart
MPCYN00CF400N- Blank CF 4 GB for Smart

Issue:
Looking for a Magelis HMI that is able to communicate to the Siemens LOGO! PLC.

Product Line:
Magelis, XBTGT, XBTGK, XBTGH, HMISTO, HMISTU, HMIGTO, HMIGTU, iPC

Resolution:

Today, Vijeo Designer V6.2 only supports one PLC model in the Siemens LOGO! series. This model is the OBA7. Currently the only driver available is the Siemens TCP/IP Ethernet driver.

To add this to your application,

1) Create a new target (HMIGTO)
2) Goto the I/O Manager and
3) Right click and select "New Driver"
4) In the dialog, select "Siemens AG" as the Manufacturer
5) For driver, select "SIMATIC S7 Ethernet"
6) For equipment, select "LOGO! OBA7"
7) Enter the IP address for the PLC in the Equipment Configuration dialog box that appears.

Regarding the different device address types. Here is a brief explanation of what they are used for:

V --> Variable memory bit address
E --> Input memory bit address
A --> Output memory bit address
M --> Memory bit address
VW --> Variable memory word address
EW --> Input memory word address
AW  ---> Output memory word address
MW  ---> Memory word address

These are the different types of memory registers available on the Siemens LOGO! OBA7

Depending on the type of variable you want to create, you would do the following:

use V, E, A, M for BIT or BOOLEAN variables
use VW, EW, AW, MW for Integer, Real, or String variables

Issue:
Is the touchscreen digitizer on the Magelis field replaceable?

Product Line:
XBTG/GC/GH/GK/GT, iPC, iDisplay, Panel PC, Front Panel, HMIGTO/GTU/STO/STU

Resolution:
No, the digitizer is  not field replaceable and the complete Magelis unit will need to be sent in for repair. Please ensure that you have a backup of the Magelis HMI program before you send in your unit. To arrange for repair please call 1800-468-5342 and use option 2.

The table below lists the various Magelis XBT G terminals and their corresponding protective sheet part numbers:

text
XBT G Terminals
text
Protective Sheet
text
XBT G2110
text
XBTZG31
text
XBT G2120/G2130/G2220/G2330
text
XBTZG32
text
XBT G4320/G4330
text
XBTZG34
text
XBT G5230/G5330/G6330
text
XBTZG36

The table below lists the various Magelis XBT G terminals and their corresponding replacement backlight bulb part numbers:

text
XBT G Terminals
text
Backlight Bulb
text
XBT G2120/G2130/G2220
text
XBTZG12
text
XBT G4320/G4330
text
XBTZG14
text
XBT G5230
text
XBTZG13
text
XBT G5330
text
XBTZG15
text
XBT G6330
text
XBTZG16

Note that these are no longer available for order from Schneider Electric.

Issue:
The time stamp of the alarm in the Alarm Summary screen object is not correct in a Magelis / Harmony HMI running Vijeo Designer Runtime, what could be the issue?

Product Line:
Harmony HMIGTO/GTU/STO/STU, iPC, Box PC, Panel PC
Magelis XBTGC/GH/GK/GT
Vijeo Designer Runtime

Environment:
Physical Human Machine Interfaces (HMI)

Cause:
The Alarm takes it's time from the System clock of the HMI.  If the system clock is not in the same time zone or clock is set incorrectly, then the time stamp on the Alarm will be incorrect.

Resolution:
For non-Windows HMI, touch-and-release the bottom-left of the screen, then 0.7 to 1.5s afterwards, touch the top-right corner of the screen (this is called the "Two corner method" in the Vijeo Designer software Help). This will bring you to the System Configuration menu which will allow you to set the Clock from the "Clock" option.

For Windows-based HMI, you must set the clock from the Windows OS.

Issue:
The Magelis target is not logging the datalogging file to the CF or SD card, why?

Product Line:
XBTGT/GK, HMIGTO/GTU/STO/STU, Magelis, datalog, compact flash card

Resolution:
There are couple reasons why the datalogging files are not logged to the CF or SD card of the Magelis.  Please check the following:
1 - In the datalogging group, under Variable Storage tab the Type is set for SRAM & File.
2 - Confirm that in Data Locations, Runtime data files are set to Secondary Drive.
3 - Go into the Runtime Configuration screen, under memory from the Online Tab it shows the Magelis recognizes the CF/SD card for Secondary Drive.

If you have confirmed the following, please call Technical Support for further assistance.

Issue
Does Schneider Electric have a skeleton key password to reset an application running on a Magelis or Harmony family HMI?

Product Line
Magelis / Harmony HMI (all models)

Environment
Physical touchscreen panel

Resolution
No, Schneider Electric does not have a skeleton key password to gain access to user applications running on Magelis / Harmony family HMI's. If you forget the password to login to your HMI, you will need to contact the original programmer to either inform you of the password or reset it for you by redownloading the entire application. Schneider Electric does not maintain the user application passwords that are installed on the HMIs. It is recommended that the Original Equipment Manufacturer or System Integrator and the End-User agree upon a password storage policy as required for future maintenance of the system.

Issue
Difference between PLC's

Product Line
Modicon Micro

Resolution
There are two main differences.
The Micro 110CPU61200 has 2K logic memory words.
The Micro 110CPU61204 has 8K logic memory words and Comm port 2 supports XMIT Block Modbus Master.

Issue
What would be the recommended CPU family to replace the 110CPUxxxxx family of PLCs?

Product line
M340, M221

Resolution
The M221 logic controllers with EcoStruxure Machine Expert - Basic programming software would be the suggestion.

Issue:
Main control board part number for ATV66 drive

Product Line:
Altivar 66, ATV66

Environment:
All

Cause:
Parts

Resolution:
There are 3 possible kit part numbers:

For ATV66U41N4 to ATV66D79N4 and ATV66U41M2 to ATV66D46M2 except ATV66D23M2S264 use VX4A66CK1;

For ATV66D23M2S264 use VX4A66CK1S260;

For ATV66C10N4 to ATV66C31N4 use VX4A66CK2

In all  of the kits listed above, the keypad is included.

Please note:
The VX4A66CK1 and VX4A66CK2 are both now obsolete.

Issue:
Quantum 140CPS11100 power supply not powering up out of box.

Product line:
Quantum

Cause:
No power at initial power up .

Resolution:
The Quantum 140CPS11100 power supply that has a PV 01 or higher require a jumper on pins 3 and 4 on the terminal strip for 115 VAC operations. If this jumper is not installed, it will be set for 220 VAC operations. Any power supply with a PV less than 1 did not require the jumpers.

The objective of this FAQ is to clarify the help in UnityPro, concerning the redundant power supplies.

We choose by exemple, the power supply ref 140CPS12420.
The output current of the 140CPS12420 is limited to 10 amp.
If a customers required a Quantum configuration with 16 amp in the rack, with a redundant power cycle system,  The solution consists to configure three power supplies 140CPS12420  in the rack.

If you unstall three power supply 140CPS12420 in a rack the load (16 amp) will be share on the three power supplies.  (5.3 amp each).
If one of the power supply fails then the load will be share with the two power supplies available (8 amp each). But at this moment, the redundancy will not be available because if a second power supply fails, the single power supply remains would not be able to deliver 16 amp.

So the solution for the customer is to unstall three 140CPS12420 in the rack.

Product Line:
Quantum

Resolution: 
Yes, you can safely remove one of the two 140CPS12400 supplies without impacting the process.. This is also true of the 140CPS12420 power supplies.

Issue
Difference between 140CPS11410 and 140CPS11420

Product Line
Modicon Quantum

Resolution
The Quantum 140CPS11410 is a 115/230 Vac, 8A summable power supply.
The Quantum 140CPS11420 is a 115/230 Vac, 11A summable power supply.

Issue

Why don't I have the option for TCP/IP in the ProWorx NxT Configuration Extension for the Quantum 140CPU11302 and the 140CPU11303 controllers?

Product Line

Quantum, ProWorx NxT

Environment

ProWorx NxT, 140CPU11302

Resolution

The problem is the wrong REV controller has been selected. The TCP/IP option is only available for the Quantum 140CPU11302 and 140CPU11303 REV 2 controllers. The TCP/IP option is not available for the REV 1 controllers in the NxT Add Configuration Extension window.

Issue:
What are the latest stripped executives for the 140CPUX1130X Quantum controllers?

Product line:
Quantum 140CPU11302, 140CPU11303, 140CPU21304

Environment:
Concept programming software

Cause:
Selecting the correct firmware to load into the Quantum controllers for IEC.

Resolution:
The PV version of the 140CPUX130X will determine what firmware you will need.

If the PV is PV06,  it is Q1RV301E.BIN.

No. The first Quantum controller that has the RRTC_DT_MS function block available in the Unity Pro Libset > System> SysClock>  picklist is the Quantum 140CPU65150.

The following chart lists all current Quantum CPUs and their processor clock speeds:

CPU Model
Processor / clock speed
140CPU11302
186 / 20 MHz
140CPU11303
186 / 20 MHz
140CPU43412A
486 / 66 MHz
140CPU53414B
586 / 133 MHz
140CPU31110
486 / 66 MHz
140CPU65150
586 / 166 MHz
140CPU65160
586 / 266 MHz
140CPU67160
586 / 266 MHz

Issue:
Replacement for the 140CPU53414A Quantum PLC.

Environment:
Quantum hardware

Cause:
Product obsolescence

Resolution:
The replacement part number is the Quantum 140CPU53414B. As of 2015 the 140CPU53414B controllers are obsolete due to parts obsolescence and it is recommended to go to the Quantum Unity
based hardware. Depending on the architecture it would be recommended to go to the M340 or the M580.

NOTE: The Quantum Unity based processors will be end of life on 12/31/18 and replaced with the M580 that is currently now being sold.

Issue
Upgrade PLC to new software package

Product Line
Modicon Quantum

Enviroment
Concept
EcoStruxure Control Expert(Unity Pro)

Resolution
No. Only the 140CPU53414A with a PV:04 or greater and all 140CPU53414B can be upgraded to support EcoStruxure Control Expert(Unity Pro).

Note: The 140cPU43412A with a PV:04 or greater can also be upgraded to support EcoStruxure Control Expert(Unity Pro).

All Quantum CPUs are FM Class 1 Div 2 approved.
140CPU11302
140CPU11303
140CPU43412A
140CPU53414A
140CPU53414B
140CPU65150
140CPU65160
140CPU652 60
140CPU67160
140CPU67260
140CPU67261
140CPU65160S (SIL 3 / ATEX Zone 2/22) This CPU meets and exceeds the FM Class 1 Div. 2 rating
140CPU67160S (SIL 3 / ATEX Zone 2/22) This CPU meets and exceeds the FM Class 1 Div. 2 rating

Title
140CRP93xxx or 140CRA931xx connection to a 140NRP9540x

Issue
140CRP93xxx or 140CRA931xx connection to a 140NRP9540x

Product Line
140CRP93100, 140CRA93100, 140CRP93200, 140CRA93200, 140NRP95401, 140NRP95400

Environment
Remote IO (S908)

Cause
N/A

Resolution
The coaxial cables with tap and trunk terminator between a 140 CRP 9•• ••/140 CRA 9•• •• and a 140 NRP 954 0• in the same backplane can be replaced by a short coaxial cable: The short coaxial cable is a RG-6 cable fitted with type F female connectors. The maximum length of this cable is 30 cm (11.8 in.).
NOTE: You can use the pre-assembled short coaxial RG-6 cable of the kit (reference RPXKITCRP) or prepare your own short coaxial cable,

Issue
What is the difference between the Quantum 140CRP93100 and 140CRP93200 Remote I/O modules?

Product line
Modicon Quantum

Environment
140CRP93100

Resolution
The main physical difference is the external connection. The 140CRP93100 has only one channel. The 140CRP93200 has two channels. The following chart lists the specification differences:

text text
140CRP93100
text
140CRP93200
text
Bus Current Required
text

600 mA
text

750 mA
text
Power Dissipation
text

3 W
text

3.8 W

Issue:
What modules will work with the Quantum 140XSM00200 discrete simulator?

Product line:
Quantum

Cause:
Looking for a simulator to work with the Quantum I/O modules and what ones will it work with.

Resolution:
The simulator module connector is designed to operate with the 140DAI54000 and the 140DAI74000 modules. These modules are 115 and 230 volts AC and field wire in the same manner. If the power source was reduced to 30 volts or less AC the module 140DAI35300 could also be used for simulating discrete inputs.

NOTE: The Quantum I/O line will be obsolete in 2021 and the x80 I/O is now e new I/O and it will work with the M340 and M580 lines. Talk with your local Schneider office or Distributor for more information.

Issue
Looking for the part number for the wiring connector for the Quantum IO Modules

Product line
Quantum IO

Resolution
The part number for the "wiring arms" or "Field Wiring Connectors" is 140XTS002 00.
This connector is used on all Quantum Discrete IO modules supporting up to 32 IO points.
It's also used on all of Quantum Analog IO

They are both Quantum AC output modules. The difference is the voltage and grouping.
140DAO84010.....24-115 VAC, 16 isolated channels.
140DAO84210.....100-230 VAC, 4x4 grouped channels.

Issue

Why is my 140NOA61110 shwoing an error E06?

Product Line

INTERBUS

Environment

140NOA61110

Resolution

This error indicates that the modules was able to confirm that it's configuration matched the real world network but, it cannot start the buss due to too many transmission errors. This typically indicates wiring problems.

Issue:
What modules will work with the Quantum 140XSM00200 discrete simulator?

Product line:
Quantum

Cause:
Looking for a simulator to work with the Quantum I/O modules and what ones will it work with.

Resolution:
The simulator module connector is designed to operate with the 140DAI54000 and the 140DAI74000 modules. These modules are 115 and 230 volts AC and field wire in the same manner. If the power source was reduced to 30 volts or less AC the module 140DAI35300 could also be used for simulating discrete inputs.

NOTE: The Quantum I/O line will be obsolete in 2021 and the x80 I/O is now e new I/O and it will work with the M340 and M580 lines. Talk with your local Schneider office or Distributor for more information.

Issue

Configuring or uploading configuration using a 140MSB10100

Product Line

Quantum

Resolution

Per MRO services, MMDS software is no longer available.
Attached is the MMDS software user guide.

The 140NOE77100 can be replaced by the 140NOE77101. The difference between these two modules are outlined below..

F​or BMXAMI0410, BMXAMO0210, BMXAMO0410, BMXAMO0802 and BMXAMM0600 modules ​below removable terminal blocks can be used.

Issue
Configuration of broken wire detection on the BMXAMO0210, BMXAMO0410, BMXAMO0802, or BMXAMM0600

Product Line
EcoStruxure Control Expert (Formally Unity Pro)

Resolution
Please take the following steps.
This is an example for the BMXAMO0210 Analog Output module.

  1. Open EcoStruxure Control Expert / Unity Pro
  2. Add a BMXAMO0210 module into an empty slot from the PLC bus screen.
    Note: In the case of an M580 PLC, it must be added using Topological Addressing rather than automatic IODDT Variable creation.
  3. Identify and remember the Topological Address of the analog module, we will need to use this in creating the Channel Status Variable. If the Analog module was inserted into the first rack (0), in slot 1 next to the PLC's CPU module, then the topological address would be '0.1'
  4. Go to the Project Browser under Variables & FB Instances
  5. Right-click on IO Derived Variables and then select Open
  6. Double-click in an empty cell under the Name column
  7. Enter a name of the channel that you wish to use Broken-Wire detection for (for example "AMO0210_Ch0")
  8. In the same row, under "Address", type in the Topological Channel Address with the notation "%CHx.y.z"
    where,
      x is the Rack Number,
      y is the Slot Number and
      z is the Channel Number.
    So if the Analog module was inserted into the first rack (0), in slot 1 next to the PLC's CPU module, and you wish to see the status of broken-wire detection on Channel 0, then enter "%CH0.1.0".
  9. In the same row, under "Type", double-click and type "T_ANA_OUT_BMX". This IODDT Structure Type is a representation of the status values from the channel of the Analog module.
  10. Close the Data Editor to accept the changes.
  11. From the PLC bus view, double-click (or Right-click Open) the AMO module to open its screen. Here, you will see that the Channel will be named the same name as you entered in Step 7 "AMO0210_Ch0".
  12. Check the checkbox under "Wiring CTRL" to activate broken-wire detection for the channel
  13. In a Program Subroutine, assign the channel variable "AMO0210_Ch0" to a the 'CH' Input Pin of a function block instance of READ_STS

The setup will now be complete.
When the program is running on the PLC, the state of the BOOLEAN element AMO_0210_Ch0.ACT_WIRE_FLT will show TRUE when a broken-wire condition occurs and can be observed in an Animation Table.

Issue
Is there a way to restore the default username and password for the web page access to the M580 Ethernet modules.

Product Line
M580 BMENOC, BMENOP0300

Environment
Windows 10 version 1902, BMEP586040, BMENOC0301

Resolution
The user lost the password and cannot access the web pages in the M580 Ethernet modules.
They need tp restore the default username and password.

In order to restore the default username and password, the M580 Ethernet module will need to be sent back for repair.

Issue: 
Replacement for the Magelis XBTGT1100 and XBTGT1130 HMI

Product Line:
XBTGT

Resolution:
XBTGT1100 is replaced by HMIGTO1300.
XBTGT1130 is replaced by HMIGTO1310.

Compatibility between the XBTGT1100/XBTGT1130 and the new HMIGTO1300/1310
-----The applications of XBTGT1100/1130 are 100% compatible on HMIGTO1300/1310 with last version of Vijeo-Designer.
-----The cut-out of HMIGTO1300/1310 and XBTGT1100/1130 is identical.
-----The network ports are identical and you can re-use the same cables. Except for the download cable which uses the USB port of HMIGTO1300/1310.
-----HMIGTO1300/1310 have the function keys.
-----HMIGTO1300/1310 have a same certifications including marine.

Goals and Symptoms

How to transfer a Vijeo designer project from a PC with the OS Win 7 (64 bits) to a target type Magelis XBTGT1000 serie using XBTZG925 cable?

Facts and Changes

When using Vijeo Designer V6.1 installed on a PC with the OS Windows 7 (64 bit) and a XBTGT1100 terminal : the problem is that we cannot install the XBTZG925 cable driver.

Causes and Fixes

This is a limitation. There is only a Win XP XBTZG925 cable driver.

The reason is that Marketing decided that the target type XBTGT1000 serie End Of Commercialization and End Of Service will be in end of 2012.
The solutions are:
1/ either edit the Vijeo designer project on a PC with Win XP Pro,
2/ either replace the XBTGT1000 serie by a terminal type XBTGT1005 serie,
3/ or replace the XBTGT1000 serie by a terminal type XBTGTO
Note that solutions 2/ & 3/ with new terminals are less expansive and higher quality.

This I/O rack expansion kit is part of the Modicon X80 modules. This kit enables 2-rack configuration, with two BMXXBE1000 rack expansion modules. It also comprises, one BMXXBC008K extension cordset, length 0.8m and one TSXTLYEX line terminator (set of 2).