Description
Analog Output Module Modicon Quantum – 4 O – 4..20 mA – 12 Bits Bipolar Current
| range of product |
Modicon Quantum automation platform
|
|
|---|---|---|
| product or component type |
Analogue output module
|
| analogue output number |
4
|
|
|---|---|---|
| addressing requirement |
4 output words
|
|
| loop voltage |
12…30 V DC
|
|
| voltage drop |
30 V 20 mA
|
|
| analogue output range |
4…20 mA 0…4096 counts, 12 bits bipolar current
|
|
| absolute accuracy error |
+/- 0.20 % of full scale at 77 °F (25 °C)
|
|
| linearity |
+/- 1 LSB
|
|
| accuracy drift according to temperature |
+/- 0.004 % of full scale/°C
+/- 0.007 % of full scale/°C maximum |
|
| isolation between channels |
500 V 47…63 Hz AC
750 V for 1 minute DC |
|
| update time |
3 ms
|
|
| setting time |
900 µs to +/- 0.1 % of the final value
|
|
| fault type |
Open circuit 4…20 mA
|
|
| bus current requirement |
480 mA
|
|
| power dissipation in W |
<= 5.3 W
|
|
| external power requirement |
12…30 V
|
|
| marking |
CE
|
|
| local signalling |
4 LEDs green channel is turned on
4 LEDs red channel fault 1 LED green bus communication is present (Active) 1 LED red external fault |
|
| module format |
Standard
|
|
| product weight |
0.66 lb(US) (0.3 kg)
|
| product certifications |
CUL
FM Class 1 Division 2 |
|
|---|---|---|
| standards |
CSA C22.2 No 142
UL 508 |
|
| resistance to electromagnetic fields |
9.14 V/yd (10 V/m) 80…2000 MHz conforming to IEC 801-3
|
|
| ambient air temperature for operation |
32…140 °F (0…60 °C)
|
|
| ambient air temperature for storage |
-40…185 °F (-40…85 °C)
|
|
| relative humidity |
95 % without condensation
|
|
| operating altitude |
<= 16404.2 ft (5000 m)
|