Sale!

140ATI03000

$ 1,946.00

Analog Input Module Modicon Quantum – 8 I Thermocouple

In stock

Category: Tag:

Description

Analog Input Module Modicon Quantum – 8 I Thermocouple

Main
range of product
Modicon Quantum automation platform
product or component type
Analogue input module
type of filter
Notch filter – 3 dB at 50/60 Hz
Single pole low pass – 3 dB at 20 Hz
Complementary
analogue input number
8
addressing requirement
10 input words
analogue input type
Thermocouple – 210…760 °C thermocouple J
Thermocouple – 270…1000 °C thermocouple E
Thermocouple – 270…1370 °C thermocouple K
Thermocouple – 270…400 °C thermocouple T
Thermocouple – 50…1665 °C thermocouple R
Thermocouple – 50…1665 °C thermocouple S
analogue input resolution
16 bits
input impedance
> 1 MOhm
absolute accuracy error
+/- 2 °C plus + 0.1 % of reading thermocouple J
+/- 2 °C plus + 0.1 % of reading thermocouple K
+/- 2 °C plus + 0.1 % of reading thermocouple T
+/- 4 °C plus + 0.1 % of reading thermocouple R
+/- 4 °C plus + 0.1 % of reading thermocouple S
+/- 2 °C plus + 0.1 % of reading thermocouple E
linearity error
1 °C, 0.1 °C, 1 F, 0.1 F – 210…760 °C
1 °C, 0.1 °C, 1 F, 0.1 F – 270…1000 °C
1 °C, 0.1 °C, 1 F, 0.1 F – 270…1370 °C
1 °C, 0.1 °C, 1 F, 0.1 F – 270…400 °C
1 °C, 0.1 °C, 1 F, 0.1 F – 50…1665 °C
accuracy drift according to temperature
0.15 µV/°C + 0.0015 % of reading/°C max low level voltage
common mode rejection
> – 120 dB 50/60 Hz
isolation between channels and bus
1780 V AC for 60 s
2500 V DC for 60 s
isolation between channels
220 V AC
300 V DC
update time
1000 ms
fault type
Broken wire
Overtacking scale
marking
CE
cold junction compensation
Internal 32…140 °F (0…60 °C)
local signalling
1 LED green bus communication is present (Active)
1 LED red external fault
8 LEDs green channel is turned on
8 LEDs red channel fault
bus current requirement
280 mA
power dissipation in W
1.5 W
module format
Standard
product weight
0.66 lb(US) (0.3 kg)
Environment
standards
CSA C22.2 No 142
UL 508
product certifications
CUL
FM Class 1 Division 2
resistance to electrostatic discharge
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2
resistance to electromagnetic fields
9.14 V/yd (10 V/m) 80…1000 MHz conforming to IEC 801-3
ambient air temperature for operation
32…140 °F (0…60 °C)
ambient air temperature for storage
-40…185 °F (-40…85 °C)
relative humidity
95 % without condensation
operating altitude
<= 16404.2 ft (5000 m)