Sale!

RXM4AB1BD

$ 25.00

Harmony, Miniature plug-in relay, 6 A, 4 CO, with lockable test button, 24 V DC RXM4AB1BD

Category: Tag:

Description

Harmony, Miniature plug-in relay, 6 A, 4 CO, with lockable test button, 24 V DC RXM4AB1BD

Main
range of product
Harmony Electromechanical Relays RXM4AB1BD
series name
Miniature
product or component type
Plug-in relay
device short name
RXM
contacts type and composition
4 C/O
[Uc] control circuit voltage
24 V DC
[Ithe] conventional enclosed thermal current
6 A at -40…55 °C
status LED
Without
control type
Lockable test button
utilisation coefficient
20 %
Complementary
shape of pin
Flat
[Ui] rated insulation voltage
250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
[Uimp] rated impulse withstand voltage
2.5 kV during 1.2/50 µs
contacts material
AgNi
[Ie] rated operational current
3 A at 28 V (DC) NC conforming to IEC
3 A at 250 V (AC) NC conforming to IEC
6 A at 28 V (DC) NO conforming to IEC
6 A at 250 V (AC) NO conforming to IEC
6 A at 277 V (AC) conforming to UL
8 A at 30 V (DC) conforming to UL
maximum switching voltage
250 V conforming to IEC
resistive rated load
6 A at 250 V AC
6 A at 28 V DC
maximum switching capacity
1500 VA/168 W
minimum switching capacity
170 mW at 10 mA, 17 V
operating rate
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
mechanical durability
10000000 cycles
electrical durability
100000 cycles for resistive load
average coil consumption in W
0.9 W
drop-out voltage threshold
>= 0.1 Uc
operate time
20 ms
release time
20 ms
average coil resistance
650 Ohm at 20 °C +/- 10 %
rated operational voltage limits
19.2…26.4 V DC
safety reliability data
B10d = 100000
protection category
RT I
test levels
Level A group mounting
operating position
Any position
CAD overall height
79 mm
CAD overall depth
78.45 mm
net weight
0.037 kg
device presentation
Complete product
Environment
dielectric strength
1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact
2000 V AC between poles
product certifications
UL
CE
GOST
CSA
Lloyd’s
standards
UL 508
EN/IEC 61810-1
CSA C22.2 No 14
ambient air temperature for storage
-40…85 °C
ambient air temperature for operation
-40…55 °C
vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
IP degree of protection
IP40 conforming to EN/IEC 60529
shock resistance
10 gn for in operation
30 gn for not operating
pollution degree
2