Description
| range of product | Modicon Quantum automation platform |
|---|---|
| product or component type | Mixed discrete I/O module |
| discrete I/O number | 24 |
| discrete input number | 16 2 groups of 8 |
|---|---|
| discrete input logic | Sink |
| addressing requirement | 1 input word 0.5 output word |
| network frequency limits | 47…63 Hz |
| discrete input voltage | 24 V DC |
| input voltage limits | 30 V <= 1 V during one cycle 56 V during 1.3 ms <= 1 V during 10 s |
| voltage state 0 guaranteed | -3…5 V |
| voltage state 1 guaranteed | 15…30 V |
| current state 0 guaranteed | <= 0.5 mA |
| current state 1 guaranteed | >= 2 mA |
| input impedance | 2500 Ohm |
| discrete output number | 8 2 groups of 4 |
| discrete output type | Solid state |
| discrete output logic | Sink |
| discrete output voltage | 24 V |
| output voltage limits | 19.2…30 V DC typical 56 V DC during 1.3 ms |
| maximum load current | <= 0.5 A per point <= 2 A per group <= 4 A per module |
| maximum voltage drop | <0.4 V 0.5 A |
| absolute maximum output | 5 A during 500 µs per point |
| maximum load inductance | 500 mH at 4 Hz |
| maximum load capacitance | 50 µF |
| maximum leakage current | 0.4 mA 30 V DC |
| response time on output | <= 1 ms at state 0 to state 1 <= 1 ms at state 1 to state 0 |
| protection type | On output by transient voltage suppression On input by resistor limited Internal output protection by 5 A fuse per group |
| associated fuse rating | 5 A per group |
| isolation between group | 500 Vrms for 1 minute |
| isolation between group and bus | 1780 Vrms for 1 minute |
| fault indication | Blown fuse on output Loss of field power on output |
| power dissipation | 1.75 W + (0.36 x input point on) + (1.1 total output load current) |
| local signalling | 1 LED (green) for bus communication is present (Active) 1 LED (red) for no voltage in output and input (F) 2 LEDs (green) for output is turned on 2 LEDs (red) for fault detected on the input point 2 LEDs (red) for fault detected on the output point |
| marking | CE |
| bus current requirement | 330 mA |
| net weight | 0.3 kg |
| resistance to electrostatic discharge | 4 kV contact conforming to IEC 801-2 8 kV on air conforming to IEC 801-2 |
|---|---|
| resistance to electromagnetic fields | 10 V/m 80…1000 MHz conforming to IEC 801-3 |
| ambient air temperature for operation | 0…60 °C |
| ambient air temperature for storage | -40…85 °C |
| relative humidity | 95 % without condensation |
| operating altitude | <= 5000 m |
| standards | CSA C22.2 No 142 UL 508 FM Class 1 Division 2 |
| product certifications | CUL |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Weight | 426.0 g |
| Package 1 Height | 16.3 cm |
| Package 1 width | 4.5 cm |
| Package 1 Length | 31.2 cm |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 7 |
| Package 2 Weight | 3.039 kg |
| Package 2 Height | 30.0 cm |
| Package 2 width | 30.0 cm |
| Package 2 Length | 40.0 cm |