Description
range of product |
Modicon Quantum automation platform
|
|
---|---|---|
product or component type |
Analogue input module
|
|
type of filter |
Single pole low pass – 3 dB at 15 Hz +/- 20 %
|
analogue input number |
8
|
|
---|---|---|
input type |
Differential
|
|
addressing requirement |
9 input words
|
|
analogue input resolution |
12 bits
|
|
linear measuring range |
4…20 mA
1…5 V |
|
absolute maximum input |
25 mA
50 V DC |
|
input impedance |
> 20 MOhm voltage
250 Ohm current +/- 0.01 % |
|
absolute accuracy error |
+/- 0.05 % of full scale
+/- 0.1 % of full scale maximum |
|
linearity error |
+/- 0.04 %
|
|
accuracy drift according to temperature |
+/- 0.0025 % of full scale/°C
<= 0.005 % of full scale/°C |
|
common mode rejection |
> – 72 dB 60 Hz
|
|
isolation between channels and bus |
1000 V DC
3000 V DC for 60 s |
|
isolation between channels |
30 V DC
|
|
update time |
5 ms
|
|
fault type |
Broken wire 4…20 mA
Undervoltage range 1…5 V |
|
marking |
CE
|
|
local signalling |
1 LED green bus communication is present (Active)
1 LED red external fault 8 LEDs green channel is turned on 8 LEDs red channel fault |
|
bus current requirement |
240 mA
|
|
power dissipation in W |
2 W
|
|
module format |
Standard
|
|
product weight |
0.66 lb(US) (0.3 kg)
|
standards |
UL 508
CSA C22.2 No 142 |
|
---|---|---|
product certifications |
CUL
FM Class 1 Division 2 |
|
resistance to electrostatic discharge |
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2 |
|
resistance to electromagnetic fields |
9.14 V/yd (10 V/m) 80…1000 MHz conforming to IEC 801-3
|
|
ambient air temperature for operation |
32…140 °F (0…60 °C)
|
|
ambient air temperature for storage |
-40…185 °F (-40…85 °C)
|
|
relative humidity |
95 % without condensation
|
|
operating altitude |
<= 16404.2 ft (5000 m)
|