Description
range of product |
Modicon Quantum automation platform
|
|
---|---|---|
product or component type |
Analogue input module
|
|
type of filter |
Single pole low pass – 3 dB at 34 Hz +/- 25 %
|
analogue input number |
16
|
|
---|---|---|
input type |
Differential
|
|
addressing requirement |
17 input words
|
|
analogue input resolution |
0…16000 counts 4…20 mA
0…20000 counts 0…20 mA 0…25000 counts 0…25 mA 0…4095 counts 4…20 mA |
|
absolute maximum input |
30 mA
|
|
input impedance |
250 Ohm
|
|
absolute accuracy error |
+/- 0.125 % of full scale
|
|
linearity error |
+/- 12 µA max 4…20 mA
+/- 6 µA max 0…20 mA +/- 6 µA max 0…25 mA +/- 6 µA max 4…20 mA |
|
accuracy drift according to temperature |
+/- 0.0025 % of full scale/°C
<= 0.0050 % of full scale /°C |
|
common mode rejection |
> – 90 dB 60 Hz
|
|
isolation between channels and bus |
1780 V AC for 60 s
|
|
update time |
15 ms 2 wires/4 wires
|
|
fault type |
Broken wire 4…20 mA
|
|
marking |
CE
|
|
local signalling |
1 LED green bus communication is present (Active)
1 LED red external fault 16 LEDs green channel is turned on 16 LEDs red channel fault |
|
bus current requirement |
360 mA
|
|
power dissipation in W |
5 W
|
|
module format |
Standard
|
|
product weight |
0.66 lb(US) (0.3 kg)
|
standards |
CSA C22.2 No 142
UL 508 |
|
---|---|---|
product certifications |
CUL
FM Class 1 Division 2 |
|
resistance to electrostatic discharge |
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2 |
|
resistance to electromagnetic fields |
9.14 V/yd (10 V/m) 80…1000 MHz conforming to IEC 801-3
|
|
ambient air temperature for operation |
32…140 °F (0…60 °C)
|
|
ambient air temperature for storage |
-40…185 °F (-40…85 °C)
|
|
relative humidity |
95 % without condensation
|
|
operating altitude |
<= 16404.2 ft (5000 m)
|