Description
| range | PowerPact |
|---|---|
| product name | PowerPact B |
| device short name | BJ 110 |
| Product or Component Type | Circuit breaker |
| Device Application | Distribution |
| Line Rated Current | 110 A |
|---|---|
| Number of Poles | 2P |
| Control Type | Toggle |
| breaking capacity code | J |
| breaking capacity | 100 kA 208Y/120 V AC 50/60 Hz UL 489 100 kA 240 V AC 50/60 Hz UL 489 65 kA 480/277 V AC 50/60 Hz UL 489 65 kA 480 V AC 50/60 Hz UL 489 25 kA 600Y/347 V AC 50/60 Hz UL 489 50 kA 250 V DC UL 489 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz UL 489 |
| Network Frequency | 50/60 Hz |
| [Ics] rated service breaking capacity | 100 kA 220…240 V AC 50/60 Hz IEC 60947-2 25 kA 500…525 V AC 50/60 Hz IEC 60947-2 10 kA 690 V AC 50/60 Hz IEC 60947-2 65 kA 380…415 V AC 50/60 Hz IEC 60947-2 65 kA 440 V AC 50/60 Hz IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947-2 |
| trip unit technology | Thermal-magnetic |
| continuous current rating | 80 % |
| [Ui] rated insulation voltage | 800 V IEC 60947-2 |
| suitability for isolation | Yes IEC 60947-2 |
| utilisation category | Category A |
| Mechanical durability | 20000 cycles IEC 947-1 Annex K ed 5.2 |
| Electrical durability | 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In |
| connection pitch | 1.06 in (27 mm) |
| AWG gauge | AWG 14…AWG 2/0 aluminium/copper |
| local signalling | Presence of auxiliary contacts flag green) |
| mounting mode | I-Line |
| electrical connection | I-Line connection line Lugs load |
| Mounting Height | 3.00 in (76.2 mm) |
| tightening torque | 31.86…38.94 lbf.in (3.6…4.4 N.m) 0.00…0.01 in² (2.5…6 mm²) (AWG 14…AWG 10) 44.25…54.87 lbf.in (5…6.2 N.m) 0.02…0.11 in² (10…70 mm²) (AWG 8…AWG 2/0) |
| number of slots | 1 auxiliary switch OF plug-in) 1 voltage release MN or MX plug-in) |
| Power wire stripping length | 0.79 in (20 mm) |
| Color | Gray RAL 7016) |
| 9 mm pitches | 6 |
| Height | 5.39 in (137 mm) |
| Width | 2.13 in (54 mm) |
| Depth | 3.50 in (89 mm) |
| Net Weight | 2.10 lb(US) (0.952 kg) |
| Quantity per Set | Set of 1 |
| phase connection | CA |
| circuit breaker application | HACR rated |
| quality labels | CE |
|---|---|
| standards | NMX J-266 GB 14048.2 CSA C22.2 No 5 UL 489 EN/IEC 60947-2 NEMA AB1 EN/IEC 60947-5-1 |
| product certifications | UL IEC CCC EAC CSA NOM |
| IP degree of protection | Front cover IP40 IEC 60529 |
| IK degree of protection | IK07 IEC 62262 |
| pollution degree | 3 IEC 60947-1 |
| ambient air temperature for operation | -13…158 °F (-25…70 °C) |
| Ambient Air Temperature for Storage | -58…185 °F (-50…85 °C) |
| operating altitude | < 6561.68 ft (2000 m) without derating 5000 m with derating |
| Category | 01135 – BJA/BKA I-LINE BREAKER |
|---|---|
| Discount Schedule | DE2 |
| Returnability | Yes |
| Country of origin | US |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.39 in (13.7 cm) |
| Package 1 Width | 2.13 in (5.4 cm) |
| Package 1 Length | 3.50 in (8.9 cm) |
| Package 1 Weight | 2.90 lb(US) (1.315 kg) |